IDP05S 2-Point Calibration
  1. Press NEXT three times and CALIB will be displayed
  2. Press ENTER and CAL ATO will be displayed
  3. Press Next and CAL LRV will be displayed
  4. Apply the lower range value pressure to the transmitter
  5. Press ENTER and CALWAIT will be displayed
  6. After 10-15 seconds, LRVdone will be displayed
  7. Press NEXT and CAL URV will be displayed
  8. Apply the upper range value pressure to the transmitter
  9. Press ENTER and CALWAIT will be displayed
  10. After 10-15 seconds, URVdone will be displayed
  11. Press NEXT until SAVE is displayed
  12. Press ENTER
  13. Complete

Schneider Electric Saudi Arabia

Explore more
Product:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales enquiry online and an expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Centre

    Find support resources for all your needs, in one place.

  • Product Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings