PowerLogic™ AccuSine PFV+
Electronic reactive current compensation solution for specific and high performance applications
Features
Technical Data
Standard RMS output current ratings
- 60 A, 120 A, 200 A, 300 A - 380 V AC to 480 V AC
- 47 A, 94 A, 157 A, 235 A - 480-600 V AC
- 40 A, 80 A, 133 A, 200 A - 600-690 V AC
Nominal voltage
- 380-480 V AC; +10%/-15%
- 480-600 V AC; +10%/-15%
- 600-690 V AC; +10%/-15%
Up to 35kV with external transformers.
Nominal Frequency
- 50/60 Hz, ±3 % auto sensing
Power factor correction
- Optimized unity PF, Leading (capacitive) or lagging (inductive) power factor (Cos f) to target.
Mains current balancing
- Negative sequence current injected to balance fundamental current on the mains due to load imbalance (inherently corrects displacement PF (Cos φ)).
Control response time
- 25 μs
Reactive correction time
- 1/4 cycle
Operating Temperature
- 60 A, 120 A & 200 A: IP00, IP20, UL Type Open, & UL Type 1 configurations -0 °C to 45 °C
- All others 0 °C to 40 °C
- Derate 2 % per degree °C to 50 °C
Relative humidity
- 0-95 %, noncondensing
Operating Altitude
- 1000 m (derate 1 %/100 m above)
Standards compliance/certification
- cULus (UL508 , CSA 22.2 No. 14)
- CE Certified, ABS, Lloyds, other local standards
Display
- 145 mm QVGA TFT 7-color touchscreen
HMI (Magelis STU)
- Plain language output (no cryptic codes)
Protection (enclosure)
- IP00, IP20, IP31, IP54, UL Type 2, UL Type 12
What is power quality?
In an ideal three phase power system, voltages are at nominal magnitude and frequency, perfectly balanced and with a perfect sinusoidal waveform. Any disturbance on one parameter (magnitude, frequency, waveform, or symmetry) is classified as a power quality issue. There are a variety of power quality disturbances – voltage dips, harmonics, transients, etc. – all of which can have negative impacts on the electrical system and equipment, such as power outage, device damage, failure, overheating, degraded performance and reduced equipment life.
AccuSine PFV+ stops power quality issues like voltage sags and flicker due to load current fluctuations (VAR compensation). For larger power quality applications, AccuSine PFV+ can be combined with a capacitor bank to reduce system cost. It can add or subtract to the capacitor bank output, achieving high speed reactive compensation with infinite resolution. It also provides high speed Powoer Factor correction where traditional capacitor banks are unable to track loads.
Benefits
- Fast ROI - displacement PF correction stops utility charges for poor PF (instant savings where penalty is charged).
- Maximizes uptime and production scheduling - mains current balancing prevents unwanted/unplanned stoppages.
- Easy expansion or retrofit - parallel connection means initial or additional unit installation with no load interruptions
- Simple and intuitive to use - touch-screen HMI with communication via RS485/RJ45 connector.
- Easy remote monitoring and operational control (via Ethernet TCP/IP).
- Flexible and scalable.
- Peace of mind - worry-free power factor correction without the risk of resonance.
Applications
- Stop voltage sags and flicker due to load current fluctuations (VAR compensation): Ball mills, shredders, arc welders, arc furnaces, hard to start AC motors, and more.
- Correction of leading power factors in data centers to allow back-up generators to operate.
- High speed power factor correction where traditional capacitor banks are unable to track loads.
- For larger applications AccuSine PFV can be combined with a capacitor bank to reduce the system cost. AccuSine PFV can either add or subtract to the capacitor bank output to achieve an high speed reactive compensation system with infinite resolution.