How do I update the firmware of my SRT/SMC/XU/XP/SMX/SMT/SCL/SRC/CHS series Smart-UPS using the Firmware Upgrade Wizard?

Issue: 

There are two methods to update the firmware of the UPS:
  • Locally via a Serial or USB connection using the Firmware Upgrade Wizard application
  • Remotely via the Network Management Card
  • The Firmware Upgrade Wizard is the most reliable and preferred method of upgrading.

If you have a previous version of the Firmware Upgrade Wizard or Firmware Images, delete the old version and download the latest revision.
If you need to upgrade via the Network Management Card, refer to Kbase #FA164737


Links to download all necessary files can be found at the end of this document.

 
Product Line:
All Smart-UPS models with the SRT, SMC, XU, XP, SMX, SMT, SCL, SRC, and CHS prefix are supported via USB or Serial communication.
 

Note:
The Firmware Upgrade Wizard does not support the below Smart-UPS devices:

  • Legacy Devices: Models with the SU, SUA, SUM, SURT, SURTD, SURTA, and SRC prefix. For example, SUA3000XL, SU2200NET, SURTD3000RMXLT.
  • Next Generation Devices: SMX750, SMX1000, and SMX1500 with firmware UPS 02.x or lower.
These units are 120 V devices built prior to date code 1037. Date code is the first 4 numbers in your serial number. For example, serial number AS1036123456 would not be supported.
  • Devices not supported in v4.2.1: SMTL1500RM3UC, SMTL1000RM2UC, SMTL750RM2UC, SCL500RM1UC, SMTL1500RMI3UC, SMTL750RMIUC, SMTL1500RMI3U, SCL500RMI1UC, SCL500RMI1UNC, SMTL1000RMI2U, SMTL1000RMI2UC, SMTL750RMI2U, SCL500RMI1U, SMTL750RMI2UC, SRC10KUXI, and SRC5KUXI.




Environment:
The system requirements for the Firmware Upgrade Wizard are as follows:

Operating systems: Microsoft Windows XP®, Windows Vista®, Windows 7®, Windows 8®, 8.1®, and Windows 10®.
 
To find your current UPS Firmware version via UPS LCD:
When you run the Firmware Upgrade Wizard, it will detect your current version.
Alternately, from the main menu of the UPS LCD screen, select "About" and scroll down to "UPS Firmware".


To find your current UPS Firmware version via Firmware Upgrade Wizard:
Run the Firmware Upgrade Wizard and it will identify the current firmware version before performing the update.


To find your current UPS ID:
Every Smart-UPS has a unique UPS ID. This can be found in the "About" menu on the UPS LCD screen, or via PowerChute.
  • You may find that the same models of UPS have different UPS IDs depending on when they were produced.
  • The final firmware version will be determined by the UPS ID and not the Model Number of the UPS.
  • If your UPS ID is not listed in the below table, it does not have an update available.
  • The Firmware Upgrade Wizard will select the correct version for the unit you are upgrading.

Firmware Revision Table
 
     UPS IDUPS PrefixLatest Firmware ReleasedAfter UpgradeFirmware Upgrade with Output On
1000SMCSMC1000UPS_10-0UPS 10.0No
1005SMCSMC1005UPS_12-0UPS 12.0No
1007SMCSMC1007UPS_11-0UPS 11.0No
1013SRTSRT1013UPS_05-1UPS 05.1No
1001SRTSRT1001UPS_02-9UPS 02.9No
1020SRTSRT1020UPS_10-1UPS 10.1No
1014SRTSRT1014UPS_05-2UPS 05.2No
1002SRTSRT1002UPS_05-2UPS 05.2No
1021SRTSRT1021UPS_12-0UPS 12.0No
1015SMT SmartConnect SMT1015UPS_04-1UPS 04.1Yes
1018SMC SmartConnectSMC1018UPS_04-1UPS 04.1Yes
1010SRTSRT1010UPS_08-3UPS 08.3Yes, from UPS 07.9 and later
1019SRTSRT1019UPS_08-2