ATV71 how can your program the normally closed contact on the R1 relay (terminals R1B to R1C) for a run status?

Issue:
On the ATV71, trying to program the normally closed contact on the R1 relay (terminals R1C to R1B) for a run status.

Product Line:
Altivar Machines, Altivar 61, Altivar 71

Environment:
All models and serial number

Cause:
N/A

Resolution:
By default on the ATV71 drives, R2 is configured as a Drive Run contact.  To change R1 to Drive running:

Go into Main Menu > Drive Menu > 1.5 Inputs/Outputs Cfg > R1 Configuration.  Select Drive running and push Enter to save.

Schneider Electric Thailand

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings