How to modify energy readings on a Powerlogic meter or move the values from one meter to another
Issue
This procedure explains how to move or transfer the energy readings from one meter to another meter. This function is supported only on some PowerLogic meters.
Product Line
Series 2000 Circuit Monitor
Series 3000 Circuit Monitor
Series 4000 Circuit Monitor
Series 800 Power Meter
Environment
Meter replacement
Readings
Cause
A meter was replaced, a master reset was performed, or a meter was cleared by accident. Any of these cases may require presetting energy readings so billing/continuity are not impacted (new meters typically start at 0 kWh).
Resolution
Perform all steps with appropriate authorization and safety procedures. Do not place references inside this section.
-
Read and record energy registers from the source meter.
- CM3/CM4/PM8: read 1700–1727.
- CM2: read 1601–1628.
Record the values using Table 1 (Recorded → Write‑To map).
-
Write the full block to the destination meter buffer.
- Write the entire 28‑register block to 8022–8049 (either one block write or 28 single writes).
- Values written to 8022–8049 must be integers within −9999…+9999; any out‑of‑range value aborts the process.
- Buffer 8022–8049 corresponds—in order—to the readings read from 1700–1727 (CM3/CM4/PM8).
- Note: CM2000 register order differs—use Table 1 mapping when preparing the block.
| CM3/CM4/PM8 | CM2 | Recorded | Write-To | |
| Registers | Readings | Readings | Registers | |
| Real Energy In | 1700 | 1601 | 8022 | |
| 1701 | 1602 | 8023 | ||
| 1702 | 1603 | 8024 | ||
| 1703 | 1604 | 8025 | ||
| Reactive Energy In | 1704 | 1605 | 8026 | |
| 1705 | 1606 | 8027 | ||
| 1706 | 1607 | 8028 | ||
| 1707 | 1608 | 8029 | ||
| Real Energy Out | 1708 | 1609 | 8030 | |
| 1709 | 1610 | 8031 | ||
| 1710 | 1611 | 8032 | ||
| 1711 | 1612 | 8033 | ||
| Reactive Energy Out | 1712 | 1613 | 8034 | |
| 1713 | 1614 | 8035 | ||
| 1714 | 1615 | 8036 | ||
| 1715 | 1616 | 8037 | ||
| Real Energy Total | 1716 | 1621* | 8038 | |
| (Signed/ Absolute) | 1717 | 1622 | 8039 | |
| 1718 | 1623 | 8040 | ||
| 1719 | 1624 | 8041 | ||
| Reactive Energy Total | 1720 | 1625* | 8042 | |
| (Signed/ Absolute) | 1721 | 1626 | 8043 | |
| 1722 | 1627 | 8044 | ||
| 1723 | 1628 | 8045 | ||
| Apparent Energy Total | 1724 | 1617* | 8046 | |
| 1725 | 1618 | 8047 | ||
| 1726 | 1619 | 8048 | ||
| 1727 | 1620 | 8049 |
* Registers are not in sequential order.
3-Commit the buffer to energy registers (destination meter). Write these decimal values:
-
- 8020 → 8017
- 8021 → 8018
- 8022 → 8019
- 6209 → 8000
4-Check status in register 8021:
-
- 0 = settings completed successfully
- 81 = Invalid Command Function (confirm 6209 was written to 8000)
- 82 = Invalid Parameters (confirm 8022–8049 values are within −9999…+9999)
5-Verify by reading the destination meter’s energy registers:
-
- 1700–1727 (CM3/CM4/PM8) or 1601–1628 (CM2).
- Values may increment immediately if the meter has load.
Note: Modbus client capable of block reads/writes (e.g., Modscan or Schneider Modbus Tester). Modbus Tester can be downloaded from FA180037.
Released for: Schneider Electric Thailand


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.