How long does the start/stop command have to be maintained in 3 wire control, to start and stop?

Resolution:
The required command duration depends on whether deceleration is enabled:

3-Wire Control Without Deceleration
- Start Command (S2): A momentary pulse is sufficient to start the motor.
- Stop Command (S1): The signal must be maintained for at least 500 ms to stop the motor correctly.

3-Wire Control With Deceleration
- Start Command (S2): A momentary pulse is sufficient.
- Stop Command (S1): A momentary pulse is also sufficient.

If external control devices are used, ensure they provide the minimum required signal duration to guarantee reliable operation.

See the attached file for further information.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Thailand

Attachment(s)
ATS01 LT Instrucion Bulletint.pdf [1.04 MB]
Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings