In Control Expert, how do I add the Ethernet and Remote IO Drops to a Quantum CPU application?
Issue:
In Unity Pro, how do I add the 140CRA31200 to a rack?
Product Line:
Unity Pro, 140CRA31200
Resolution:
To enable Ethernet RIO you must add a 140CRP31200 to the local rack. There will be another node below the Local Quantum Drop called EIO bus. Open the EIO bus, <double-click> on the drop (square box) and select your slot size. Once that is complete, you will see the Quantum slot rack with a 140CRA31200.
To enable S908 RIO you must add a 140CRP93x00 to the local rack. There will be another node below the Local Quantum Drop called RIO bus. Open the RIO bus, <double-click> on the drop (square box) and select your slot size. Once that is complete, you will see the Quantum slot rack with a 140CRA93100.