How can the logic inputs status of the Altivar Drives be monitored via network communications?

Issue:
Wanting to know how can the logic inputs status of the Altivar Drives be monitored via network communications?

Product Line:
ATV61, ATV71, ATV32

Environment:
All Serial numbers

Cause:
N/A

Resolution:
The logic input status can be monitored by Modbus address 5202.
Bit 0 - LI1
Bit 1 - LI2
Bit 2 - LI3
Bit 3 - LI4
Bit 4 - LI5
Bit 5 - LI6
If extended IO cards are used
Bit 6 - LI7
Bit 7 - LI8
Bit 8 - LI9
Bit 9 - LI10
Bit 10 - LI 11
Bit 11 - LI 12
Bit 12 - LI 13
Bit 13 - LI 14

Schneider Electric Thailand

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings