How to configure the IOScanning table to a 140NOE77101 exchanging with a 140NOC77711 ?
By default the Unit ID value on 140NOE77101’s IO Scanning table is 255. Keeping this configuration it is impossible to READ or WRITE data inside a PLC application through a 140NOC77111.
It is mandatory to change the Unit ID value from 255 to 1 on 140NOE77101’s IO Scanning table.
It is mandatory to change the Unit ID value from 255 to 1 on 140NOE77101’s IO Scanning table.
Released for: Schneider Electric Thailand






Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.