How can we help you today?

Why do the Quantum high end CPU Eth Coprocessor and the 140NOE, when they ioscan the same DIO toward %I, end with reversed result

20 years ago, the 2 products were designed differently, one is little endian while the other is big endian.
the customer is advised to always store the ioscan result in %MW instead of %I not to face this issue.

Schneider Electric Thailand

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings