Why do Waveform Captures on the ION7350 show 0 V for only the B phase

Issue
When a waveform capture is created on an ION7350 monitoring a 3-phase system, there is a reading of 0 V on the B-phase waveform.

Product Line
ION7350

Environment
Power Monitoring Expert 7.2.x, 8.0, 9.0, 2020, 2021, 2022, 2023
Struxureware Power Monitoring Expert 7.0.x
ION Enterprise 5.x, 6.0.x

Cause
The ION7350 is configured with a Delta Volts Mode. While Delta Volts Mode will calculate the B phase voltage for monitoring, it will not use calculated values for the waveform capture.

Resolution
If the ION7350 is connected to a 4-wire Wye circuit, the the resolution is to rewire the ION7350 for a 4-wire circuit and reconfigure the meter to be a Wye Volts Mode.
However, if the ION7350 is wired to a 3-Wire Delta circuit, the device must remain configured as Delta Volts Mode and B phase voltage will remain unavailable.

Schneider Electric Thailand

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings