Issue: It is not possible to perform the Active Trip Curve Test for Earth Leakage protection using Ecoreach.
Cause: The Dual Setting is not enabled from the Micrologic X HMI and the Set B is set to active. To perform the Active Trip Curve Test for Earth Leakage protection using Ecoreach switch set A to be active using Ecoreach.
Cause: The Dual Setting is not enabled from the Micrologic X HMI and the Set B is set to active. To perform the Active Trip Curve Test for Earth Leakage protection using Ecoreach switch set A to be active using Ecoreach.
Released for: Schneider Electric Thailand


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.