{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

What is the operating time of ground fault protection devices defined in the UL 1053 standard?

The UL 1053 standard defines in Table 22.1 the operating time of the ground fault protection devices:
Ground-fault current (A)Time (s)
85% of pickup currentShall not trip
115% of pickup currentUltimately
150% of pickup current2
250% of pickup current1

Schneider Electric Thailand

Related products for Schneider Electric Thailand
Range:
Multi93350 PDM - Legacy
Related products for Schneider Electric Thailand
Range:
Multi93350 PDM - Legacy
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.