Importing a 'Control Expert Classic' project returns the following error:

This occurred because the 'Control Expert Classic project' was not built using Control Expert 15.1 Classic with the I/O Scanning Mode set to Enhanced before creating the export file (.zef). This is required because:
Use the following steps to set the IO Scanning mode to enhanced:
    This occurred because the 'Control Expert Classic project' was not built using Control Expert 15.1 Classic with the I/O Scanning Mode set to Enhanced before creating the export file (.zef). This is required because:
- The I/O scanning mode cannot be changed after import.
 - The Topology Manager only supports Enhanced mode.
 
Use the following steps to set the IO Scanning mode to enhanced:
- Open the project with Control Expert Classic 15.1.
 - Open the project settings.
 - Click on Build Settings.
 - Click on IO Scanning mode.
 - Select Enhanced from the drop down menu.
 - Click on Apply.
 - Save the changes.
 - Export the project as a '.zef'.
 