Issue:
Clarify the firmware execution cycle behavior for Sepam Series 80 protection relays and what functional groups execute each cycle.

Product Line:
Sepam Series 80

Environment:
Sepam Series 80 protection relays
Firmware execution of protection, logic, I/O, and measurement functions

Cause:
Project and commissioning teams require a concise description of the relay’s deterministic execution cycle to support coordination studies and to estimate end‑to‑end behavior of protection and control logic.

Resolution:

  1. Sepam Series 80 firmware operates cyclically and deterministically, running protection algorithms, control logic, I/O scanning, and device self‑checks in a repeating execution loop.
  2. Fast functions executed every cycle include the protection elements, logic input scanning, control logic (including the logic equation editor/Logipam constructs), and logic output updates, alongside device self‑diagnostics.
  3. Measurement and other slow/housekeeping tasks are distributed across cycles.
  4. When a quantified timing value is required for an engineering study, perform a bench verification on a representative relay and firmware build by toggling a digital input, driving a simple control logic action, and measuring the repeatable delay at a digital output or in time‑tagged event data. Record the firmware version/build and configuration with the results.

Schneider Electric Turkey

Daha fazlasını keşfedin
Seri:
Daha fazlasını keşfedin
Seri:
  • Ürün Belgeleri
  • Yazılım İndirmeleri
  • Ürün Seçici
  • İkame Ürün ve Değiştirme
  • Yardım Merkezi
  • Ofislerimizi Bulun
  • Teklif Alın
  • Satış noktaları
  • Schneider Electric Topluluğu
  • Kariyer
  • Şirket Profili
  • Bir usulsüzlüğü bildirin
  • Erişilebilirlik
  • Haberler
  • Yatırımcılar
  • EcoStruxure
  • İş Araması
  • Blog
  • Gizlilik İlkesi
  • Çerez Bildirimi
  • Change your cookie settings