Markalar

Schneider Electric Web Sitesine Hoş Geldiniz

Web sitemize hoş geldiniz.
		
Size bugün nasıl yardımcı olabiliriz?
How to configure the STBEHC3020 for quadrature mode.

Issue
How to configure the EHC3020 for quadrature mode.

Product Line
All versions of the Advantys Configuration Software

Environment
Windows 7

Resolution
The following steps show how the the 'STBEHC3020' High Speed Counter module can be configured

for quadrature mode. Test mode is 'used' to simulate the fieldbus and hardware inputs.

  • Wire the 'EHC3020' to the incremental encoder.

xzcv

sadf
  • Double click on the 'EHC3020' module to open the properties window for the module.
sadfg
  • Configure the parameters as shown.
  • Download the application to the island.
sadf

· Start the PLC.
· Place the PLC into 'Test' mode.
sdfg
  • Set the Input Validation bits to Off.
sdf


Enable the Counter Reset bit to 'On'.
sdfgh

Enable the Counter Enable bit to 'On'
sdfg

To reset the counter, toggle the Counter Reset bit from 0 to 1.

Schneider Electric Turkey

Daha fazlasını keşfedin
Seri:
Daha fazlasını keşfedin
Seri:
  • Ürün Belgeleri
  • Yazılım İndirmeleri
  • Ürün Seçici
  • İkame Ürün ve Değiştirme
  • Yardım Merkezi
  • Ofislerimizi Bulun
  • Teklif Alın
  • Satış noktaları
  • Schneider Electric Topluluğu
  • Kariyer
  • Şirket Profili
  • Bir usulsüzlüğü bildirin
  • Erişilebilirlik
  • Haberler
  • Yatırımcılar
  • EcoStruxure
  • İş Araması
  • Blog
  • Gizlilik İlkesi
  • Çerez Bildirimi
  • Change your cookie settings