Attempt to launch the OFS server, returns the error: Unable to Locate Component O6CLIEN1.dll
Issue
Attempt to launch the OFS server, returns the following error: Unable to Locate Component O6CLIEN1.dll
Product Line
OFS
Environment
Windows 7, 10
Resolution
Attempt to launch the OFS server, returns the following error:
"Ofs.exe - Unable to Locate Component"
The message section of the error says: "
This application has failed to start because O6CLIEN1.dll was not found.
Uninstalling and Re-installing the OFS does not resolve problem."
Causes and Fixes
This is a result of a bad pathname entered into the Microsoft Windows registry for the applicable dll's. Usually, the problem is
due to the prefix foldername (i.e. C:\Program Files\Common Files) being incrorrectly defined.
- Start the registry editor
WARNING: BE VERY CAREFUL WHEN USING THE REGiSTRY EDITOR IF THESE STEPS ARE NOT FOLLOWED
EXACTLY, YOU MAY INADVERTENTLY DELETE OR MODIFY SOMETHING ELSE WHICH CAN CORRUPT
YOUR WINDOWS OPERATING SYSTEM.
- Search the registry
- Make sure that the following path is entered into the path definition correctly.
C:\Program Files\Common Files\Schneider Electric Shared\SSTA\
- If the path is incorrect, right click on the name and select 'Modify' to change it.
- Repeat the search for anymore instances of the path and correct it as needed.
Repeat the above procedure for the following path.
C:\Program Files\Common Files\Schneider Electric Shared\SRCSDK\
- Search the registry
- Make sure that the following path is entered into the path definition correctly
- If the path is incorrect, right click on the name and select 'Modify' to change it.
- Repeat the search for anymore instances of the path and correct it as needed.
Yayımlanma amacı: Schneider Electric Turkey


Yardıma mı ihtiyacınız var?
Ürün seçici
Uygulamalarınız için doğru ürünleri ve aksesuarları hızlı ve kolay bir şekilde bulun.
Teklif Alın
Satışla ilgili sorularınızı çevrimiçi olarak başlatın, bir uzman sizinle bağlantı kuracaktır.
Satış noktaları
Konumunuza en yakın Schneider Electric distribütörünü kolayca bulun.
Yardım Merkezi
Tüm ihtiyaçlarınız için destek kaynaklarını tek bir yerde bulun.