How to connect Unity Pro to a Modbus PLC through a TSXETG100 Ethernet gateway

Issue

How can Unity Pro connect to a Modbus PLC through a TSXETG100 Ethernet gateway?

Product Line

  • TSXETG100
  • Unity Pro

Environment

The TSXETG100 is used as the communication gateway between Unity Pro and the PLC.

Resolution

  1. Configure the PLC Modbus address in the TSXETG100

    • Open the TSXETG100 web interface by entering its IP address in a web browser.

ETG0100, connection

      • Log in to the TSXETG100.
      • Select Setup > Device List.

web page, ETG,

      • Add the Modbus address of the PLC to the device list.
      • Select Apply to save the configuration.
  1. Configure the PLC address in Unity Pro

    • Open the Unity Pro project.
    • Select PLC > Set Address.
    • unity Pro, Set address
    • In Media, select TCPIP.
    • In the Address field, enter the TSXETG100 IP address followed by a semicolon (;) and the PLC Modbus address.
    • connection configuration

    In this example:

    • 192.168.40.2 is the TSXETG100 IP address.
    • 1 is the Modbus address of the PLC.
  2. Connect to the PLC

    • Confirm the address configuration.
    • Select PLC > Connect.


Schneider Electric Turkey

Daha fazlasını keşfedin
Seri:
Daha fazlasını keşfedin
Seri:
  • Ürün Belgeleri
  • Yazılım İndirmeleri
  • Ürün Seçici
  • İkame Ürün ve Değiştirme
  • Yardım Merkezi
  • Ofislerimizi Bulun
  • Teklif Alın
  • Satış noktaları
  • Schneider Electric Topluluğu
  • Kariyer
  • Şirket Profili
  • Bir usulsüzlüğü bildirin
  • Erişilebilirlik
  • Haberler
  • Yatırımcılar
  • EcoStruxure
  • İş Araması
  • Blog
  • Gizlilik İlkesi
  • Çerez Bildirimi
  • Change your cookie settings