Markalar

Schneider Electric Web Sitesine Hoş Geldiniz

Web sitemize hoş geldiniz.
		
Size bugün nasıl yardımcı olabiliriz?
How is an Altivar VFD set to always run a particular speed when no reference input is connected?

Article available in these languages: Japonca

Issue:
Wants the Altivar VFD set to always run at a particular speed when no reference input is connected.

Product Line:
Altivar 12, 32, 312, 61, 71, 212, 320

Environment:
All models

Cause:
VFD does not run the motor without a speed reference.

Resolution:
If there is no external speed reference when the VFD gets a run command, then it will always run at the minimum speed programmed to the VFD.  Set the minimum speed parameter to the desired run speed.  Use parameter LSP for the Altivar12, 32, 312, 320, 61, 71 drives.  Use parameter LL for the Altivar 212 drive.  These can be adjusted while the motor is running.

Schneider Electric Turkey

Daha fazlasını keşfedin
Seri:
Daha fazlasını keşfedin
Seri:
  • Ürün Belgeleri
  • Yazılım İndirmeleri
  • Ürün Seçici
  • İkame Ürün ve Değiştirme
  • Yardım Merkezi
  • Ofislerimizi Bulun
  • Teklif Alın
  • Satış noktaları
  • Schneider Electric Topluluğu
  • Kariyer
  • Şirket Profili
  • Bir usulsüzlüğü bildirin
  • Erişilebilirlik
  • Haberler
  • Yatırımcılar
  • EcoStruxure
  • İş Araması
  • Blog
  • Gizlilik İlkesi
  • Çerez Bildirimi
  • Change your cookie settings