Why does the Analog output AO1 not deliver 10Vdc at 60 hz on ATV12 drive?
Issue:
Wondering why does the Analog output AO1 not deliver 10Vdc at 60 hz?
Product Line:
ATV12
Environment:
All
Cause:
Output is configured for Motor frequency and 0-10Vdc.
Resolution:
The tFr parameter must be set to 60 hz. The Analog output is scaled between 0 to Max Frequency (tFr).
Wondering why does the Analog output AO1 not deliver 10Vdc at 60 hz?
Product Line:
ATV12
Environment:
All
Cause:
Output is configured for Motor frequency and 0-10Vdc.
Resolution:
The tFr parameter must be set to 60 hz. The Analog output is scaled between 0 to Max Frequency (tFr).
Yayımlanma amacı: Schneider Electric Turkey

