Where Can I Find Selection Information for dV/dT Motor Protection Filters for Altivar Drives in the US and Canada?
Resolution:
In the United States, most motor protection output filters (dV/dT filters) listed in Schneider Electric’s global catalogs are not available. Instead, Schneider Electric partners with a third-party supplier to provide compatible solutions.
Details:
- Supported Drives: ATV12, ATV32, ATV312, ATV61, ATV71, ATV320, ATV340, ATV630, ATV930
- Supplier: TCI (Transcoil Inc.) – www.transcoil.com
- Availability: Filters can be purchased through your local Schneider Electric distributor
How to Select the Right Filter:
- For 460 VAC systems: Choose the filter based on motor horsepower (HP). Check the attached document.
- For 230 VAC systems: Use the motor’s full load current (FLC) to determine the correct filter size
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Yayımlanma amacı: Schneider Electric Turkey
Ekler
Daha fazlasını keşfedin
Seri:
Daha fazlasını keşfedin
Seri:
Yardıma mı ihtiyacınız var?
Ürün seçici
Uygulamalarınız için doğru ürünleri ve aksesuarları hızlı ve kolay bir şekilde bulun.
Teklif Alın
Satışla ilgili sorularınızı çevrimiçi olarak başlatın, bir uzman sizinle bağlantı kuracaktır.
Satış noktaları
Konumunuza en yakın Schneider Electric distribütörünü kolayca bulun.
Yardım Merkezi
Tüm ihtiyaçlarınız için destek kaynaklarını tek bir yerde bulun.