Markalar

Schneider Electric Web Sitesine Hoş Geldiniz

Web sitemize hoş geldiniz.
		
Size bugün nasıl yardımcı olabiliriz?
How is the analog output scaled on the ATV312 drives?

Article available in these languages: İspanyolca

Issue:
Customer is trying to confirm how the AO is scaled on the ATV312 drives.

Product line:
Altivar 312, ATV312

Environment:
All model numbers, all serial numbers

Cause:
n/a

Resolution:

Setting of the parameter dO, under the I-O- menu:
The two more common settings are Motor current (oCr) and Motor Frequency (oFr).
oCr, 20mA or 10V corresponds to 2 times the Drive rated current (In)
oFr - the max output of 20mA or 10V is scaled to tFr (Max Frequency)

For the rest of the settings, consult the ATV312 Installation manual, or see the attached image.

Schneider Electric Turkey

Ekler
ATV312 Analog Output Settings.jpg [115.53 KB]
Daha fazlasını keşfedin
Seri:
Daha fazlasını keşfedin
Seri:
  • Ürün Belgeleri
  • Yazılım İndirmeleri
  • Ürün Seçici
  • İkame Ürün ve Değiştirme
  • Yardım Merkezi
  • Ofislerimizi Bulun
  • Teklif Alın
  • Satış noktaları
  • Schneider Electric Topluluğu
  • Kariyer
  • Şirket Profili
  • Bir usulsüzlüğü bildirin
  • Erişilebilirlik
  • Haberler
  • Yatırımcılar
  • EcoStruxure
  • İş Araması
  • Blog
  • Gizlilik İlkesi
  • Çerez Bildirimi
  • Change your cookie settings