Can you set up the ATV630 and ATV930 Process drive to run a motor with voltage limitation?
Issue:
ATV630 and ATV930 drives to run a motor with voltage limitation

Product Line:
ATV630 and ATV930

Environment:
All

Cause:
Needs to limit the voltage coming out of the drive.

Resolution:



Hello,
Unfortunately the parameter [UCP] Voltage at constant power - which was available in ATV61/71 - doesn't exist in the ATV6xx/ATV9xx.
The only possible work around is the usage of the V/f 5-points characteristic.
Exemplary parameter setting:
[U1] = 115V and [F1] = 25Hz
[U2] = 230V and [F2] = 50Hz
[U3] = 230V and [F3] = 51Hz
[U4] = 230V and [F4] = 75Hz
[U5] = 230V and [F5] = 100Hz
Please consider that the nominal point of the motor data MUST be the last value on this V/f characteristic. The nominal motor voltage [UNS] >= [U5] and the nominal frequency [FRS] >= [F5]. The nominal speed must be calculated according to the adjusted nominal speed.
[UNS] = 230V, [FRS] = 100Hz, [NSP] = 2980 rpm.
An auto tuning function needs not to be performed. Due to the "wrong" motor data it makes no sense.

Schneider Electric Turkey

Can you set up the ATV630 and ATV930 Process drive to run a motor with voltage limitation?
Issue:
ATV630 and ATV930 drives to run a motor with voltage limitation

Product Line:
ATV630 and ATV930

Environment:
All 

Cause:
Needs to limit the voltage coming out of the drive.

Resolution:



 
Hello,
Unfortunately the parameter [UCP] Voltage at constant power - which was available in ATV61/71 - doesn't exist in the ATV6xx/ATV9xx.
The only possible work around is the usage of the V/f 5-points characteristic.
Exemplary parameter setting:
[U1] = 115V and [F1] = 25Hz
[U2] = 230V and [F2] = 50Hz
[U3] = 230V and [F3] = 51Hz
[U4] = 230V and [F4] = 75Hz
[U5] = 230V and [F5] = 100Hz
Please consider that the nominal point of the motor data MUST be the last value on this V/f characteristic. The nominal motor voltage [UNS] >= [U5] and the nominal frequency [FRS] >= [F5]. The nominal speed must be calculated according to the adjusted nominal speed.
[UNS] = 230V, [FRS] = 100Hz, [NSP] = 2980 rpm.
An auto tuning function needs not to be performed. Due to the "wrong" motor data it makes no sense.
 
 
  

Schneider Electric Turkey

Schneider Electric Türkiye ile İlgili Ürünler
Seri:
Schneider Electric Türkiye ile İlgili Ürünler
Seri:
Schneider Electric Türkiye ile İlgili Ürünler
Seri:
Schneider Electric Türkiye ile İlgili Ürünler
Seri:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.