How can I install a EStop on an Altistart softstarter?
Issue:
Install EStop on an Altistart softstarts.
Product Line:
ATS48 ATS22 ATS01
Environment:
All series
Cause:
Customer would like the softstart to shut down (stop) on any external fault trips.
Resolution:
Series the external fault contacts (normally closed) with the run / stop command to open on a external fault.
Install EStop on an Altistart softstarts.
Product Line:
ATS48 ATS22 ATS01
Environment:
All series
Cause:
Customer would like the softstart to shut down (stop) on any external fault trips.
Resolution:
Series the external fault contacts (normally closed) with the run / stop command to open on a external fault.