Markalar

Schneider Electric Web Sitesine Hoş Geldiniz

Web sitemize hoş geldiniz.
		
Size bugün nasıl yardımcı olabiliriz?
Galaxy VX; Customer, consultant or engineer looking for the center of gravity (CoG) for the IO and/or PC enclosures

Article available in these languages: İspanyolca


Issue:
Customer, consultant or engineer looking for the Center of Gravity (CoG) for the IO and/or PC enclosures.


Product line:
Galaxy VX


Environment:
All models, all serial numbers


Cause:
none.


Resolution:
The enclosures have the following CoG.
  • GVX PC: X-distance 290mm, Y-distance 930mm , Z-distance 440mm
  • GVX 750kW IOC: X-distance 590mm, Y-distance 830mm, Z-distance 390mm
  • GVX 1000kW IOC: X-distance 590mm, Y-distance 830mm, Z-distance 390mm
  • GVX 1500kW IOC: X-distance 1060mm, Y-distance 970mm, Z-distance 430mm
  • GVXMBCR750: X-distance 399.7mm, Y-distance 993mm, Z-distance 471.5mm

(X=width, Y=height, Z=depth)



Schneider Electric Turkey

Daha fazlasını keşfedin
Seri:
Daha fazlasını keşfedin
Seri:
  • Ürün Belgeleri
  • Yazılım İndirmeleri
  • Ürün Seçici
  • İkame Ürün ve Değiştirme
  • Yardım Merkezi
  • Ofislerimizi Bulun
  • Teklif Alın
  • Satış noktaları
  • Schneider Electric Topluluğu
  • Kariyer
  • Şirket Profili
  • Bir usulsüzlüğü bildirin
  • Erişilebilirlik
  • Haberler
  • Yatırımcılar
  • EcoStruxure
  • İş Araması
  • Blog
  • Gizlilik İlkesi
  • Çerez Bildirimi
  • Change your cookie settings