Markalar

Schneider Electric Web Sitesine Hoş Geldiniz

Web sitemize hoş geldiniz.
		
Size bugün nasıl yardımcı olabiliriz?
Altivar process, does FDR (fast device replacement) work towards new firmware version?
We can confirm that latest Ethernet channel evolution's have brought FDR service improvements.
With todays fw versions :
ATV6xx:  version 2.2ie24 (internally, the embedded Ethernet firmware version must be 1.Die15)
ATV9xx: version 1.8ie14 (internally, the embedded Ethernet firmware version must be 1.Die15)
Eth.card VW3A3720: version 1.Die15
or any newer version, the FDR will work towards equal or newer fw version.

Example1: today ATV2.2IE24 is used and after one year it will be replaced by ATV with newer fw (e.g. 2.3IExx). Result is that FDR OK
Example2 : ATV1.9IE24 has been used and now it is going to be replaced by ATV 2.2IE24. Result is that FDR is not OK.

Schneider Electric Turkey

Daha fazlasını keşfedin
Seri:
Daha fazlasını keşfedin
Seri:
  • Ürün Belgeleri
  • Yazılım İndirmeleri
  • Ürün Seçici
  • İkame Ürün ve Değiştirme
  • Yardım Merkezi
  • Ofislerimizi Bulun
  • Teklif Alın
  • Satış noktaları
  • Schneider Electric Topluluğu
  • Kariyer
  • Şirket Profili
  • Bir usulsüzlüğü bildirin
  • Erişilebilirlik
  • Haberler
  • Yatırımcılar
  • EcoStruxure
  • İş Araması
  • Blog
  • Gizlilik İlkesi
  • Çerez Bildirimi
  • Change your cookie settings