SSS'leri Arayın
How to roll back NetBotz firmware.
Issue:
How to roll back NetBotz firmware.
Product Line:
Netbotz
Environment:
NetBotz 3xx, 4xx, and 5xx firmware
Cause:
If for some reason you feel the need to revert back to a previous firmware (BotzWare) revision on a NetBotz appliance, you can not simply use the upgrade feature.
Resolution:
Follow the detailed instructions for the TFTP procedure highlighted in FA176133.
Replace step 1 with the version of BotzWare to which you are looking to downgrade. Older revisions may be available at: www.apc.com/tools/download
Please note that when downgrading, it is suggested that you not keep any of the old configuration and do not use the "rootupgkeep" option in step 17.
How to roll back NetBotz firmware.
Product Line:
Netbotz
Environment:
NetBotz 3xx, 4xx, and 5xx firmware
Cause:
If for some reason you feel the need to revert back to a previous firmware (BotzWare) revision on a NetBotz appliance, you can not simply use the upgrade feature.
Resolution:
Follow the detailed instructions for the TFTP procedure highlighted in FA176133.
Replace step 1 with the version of BotzWare to which you are looking to downgrade. Older revisions may be available at: www.apc.com/tools/download
Please note that when downgrading, it is suggested that you not keep any of the old configuration and do not use the "rootupgkeep" option in step 17.
Yayımlanma amacı:Schneider Electric Turkey
Schneider Electric Türkiye ile İlgili Ürünler
Seri:
Schneider Electric Türkiye ile İlgili Ürünler
Seri: