why does my safety hotstandby CPU takes a longer time to startup than usual when the interlink in not present
1. Issue
a misuse side effect was discovered: when replacing a CPU with an inoperative (incorrectly plugged or missing) interlink, the new CPU could (also) start as primary and perturbative the RIO drops..
2. Product Line
All M580 Hotstandby CPUs : BMEHx0x0
3. Environment
Since SV2.80
this delay will be optimized as part of the next firmware release (SV2.90 or 3.00, to be confirmed), and the additional boot duration should be removed.
4. Resolution
With previous versions, in these conditions, the CPU boot duration was about 30 seconds, while with SV 2.80, on missing interlink, an additional delay was implemented, that adds from 4 to 27 seconds (depending on the amount of RIO drops) to the boot duration
5. FAQ Applicable Conditions (Optional )
NA
a misuse side effect was discovered: when replacing a CPU with an inoperative (incorrectly plugged or missing) interlink, the new CPU could (also) start as primary and perturbative the RIO drops..
2. Product Line
All M580 Hotstandby CPUs : BMEHx0x0
3. Environment
Since SV2.80
this delay will be optimized as part of the next firmware release (SV2.90 or 3.00, to be confirmed), and the additional boot duration should be removed.
4. Resolution
With previous versions, in these conditions, the CPU boot duration was about 30 seconds, while with SV 2.80, on missing interlink, an additional delay was implemented, that adds from 4 to 27 seconds (depending on the amount of RIO drops) to the boot duration
5. FAQ Applicable Conditions (Optional )
NA
Yayımlanma amacı: Schneider Electric Turkey
Daha fazlasını keşfedin
Seri:
Daha fazlasını keşfedin
Seri:
Yardıma mı ihtiyacınız var?
Ürün seçici
Uygulamalarınız için doğru ürünleri ve aksesuarları hızlı ve kolay bir şekilde bulun.
Teklif Alın
Satışla ilgili sorularınızı çevrimiçi olarak başlatın, bir uzman sizinle bağlantı kuracaktır.
Satış noktaları
Konumunuza en yakın Schneider Electric distribütörünü kolayca bulun.
Yardım Merkezi
Tüm ihtiyaçlarınız için destek kaynaklarını tek bir yerde bulun.