SBO upgrade process failed (SBO 1.8.x to SBO 1.9.x)

Upgrade failed when upgrading Automation Server from SBO version 1.8.x to 1.9.x

Log indicates:
(Device Administrator | View | Last Upgrade Log)
ERROR:        Exception encountered during database upgrade: StartUpMode UpgradeDatabase : RecoverableException: d:\dev\rb-rb-1.9.2-system\source\server\nsp_servers\csc\LonTypes\source\Lon2MapFileUtil.cpp(185) Invalid Data Error: Invalid_Data (0x10000) in module Impex(57). "Map data is too old for type: public.lon2.devicetemplates.pid90003A8200E90401. You need to run the Lon Repair command in the latest version of the workstation"
2019-04-10 07:14:02  INFORMATION:  Database upgrade time: 5.28889 seconds
2019-04-10 07:14:02  INFORMATION:  =============  End Configuration Database Upgrade  =============
Source version: 1.8.1.79 Target Version: 1.9.2.45

Steps
1. Upgrade Workstation and Automation Server to the latest available version (SBO 1.8.1.3600)
2. Connect with Workstation to Automation Server
3. Select Server, and right-click Advanced | Repair LonWorks configuration ...
4. Select Next to repair when indicated "Server needs to be repaired"
5. Finally upgrade to Version 1.9 using Device Administrator

Schneider Electric Turkey

Ekler
Start repair.PNG.png [120.18 KB]
repair01.PNG.png [37.8 KB]
Daha fazlasını keşfedin
Seri:
Daha fazlasını keşfedin
Seri:
  • Ürün Belgeleri
  • Yazılım İndirmeleri
  • Ürün Seçici
  • İkame Ürün ve Değiştirme
  • Yardım Merkezi
  • Ofislerimizi Bulun
  • Teklif Alın
  • Satış noktaları
  • Schneider Electric Topluluğu
  • Kariyer
  • Şirket Profili
  • Bir usulsüzlüğü bildirin
  • Erişilebilirlik
  • Haberler
  • Yatırımcılar
  • EcoStruxure
  • İş Araması
  • Blog
  • Gizlilik İlkesi
  • Çerez Bildirimi
  • Change your cookie settings
  • Tercih Merkezi