Size bugün nasıl yardımcı olabiliriz?

What's the difference between Basic and Professional Licenses in EcoStruxure Operator Terminal Expert?

Issue
What's the difference between Basic and Professional Licenses in EcoStruxure Operator Terminal Expert?

Product Line
EcoStruxure Operator Terminal Expert

Environment
Configuration software on Windows PC

Resolution
The Basic License allows download only to Basic Panels in the ranges:

  • Magelis ST6
  • Magelis STO7


The Professional License allows download to all supported EcoStruxure Machine Operator Terminal HMIs:

  • Magelis ST6
  • Magelis STO7
  • Magelis iPC
  • Magelis GTU
  • Magelis HMIGTUX

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Turkey

Daha fazlasını keşfedin

Yardıma mı ihtiyacınız var?

Ürün seçici

Uygulamalarınız için doğru ürünleri ve aksesuarları hızlı ve kolay bir şekilde bulun.

Teklif Alın

Satışla ilgili sorularınızı çevrimiçi olarak başlatın, bir uzman sizinle bağlantı kuracaktır.

Satış noktaları

Konumunuza en yakın Schneider Electric distribütörünü kolayca bulun.

Yardım Merkezi

Tüm ihtiyaçlarınız için destek kaynaklarını tek bir yerde bulun.