Why is my EcoStruxure Control Expert project opening in Read-only mode ?

Issue:
EcoStruxure Control Expert project opening in Read-only mode


Product Line:
EcoStruxure Control Expert, Unity Pro


Resolution:
When opening a EcoStruxure Control Expert project, you have the option to open the project in read-only mode as shown below.

image1

If this option is not selected and the project is still opening in read-only mode, follow the steps below
1. Close the project.
2. Locate the .stu project file on your computer
3. Right click on the project file and select properties
4. uncheck the "Read-only" attribute under the "General" tab of the file properties
5. Select "apply", then OK
6. Open the .stu project file in Control Expert and it should now open in Read/Write mode

Schneider Electric Turkey

Daha fazlasını keşfedin
Seri:
Daha fazlasını keşfedin
Seri:

Yardıma mı ihtiyacınız var?

Yardıma mı ihtiyacınız var?

Ürün seçici

Ürün seçici

Uygulamalarınız için doğru ürünleri ve aksesuarları hızlı ve kolay bir şekilde bulun.

Teklif Alın

Teklif Alın

Satışla ilgili sorularınızı çevrimiçi olarak başlatın, bir uzman sizinle bağlantı kuracaktır.

Satış noktaları

Satış noktaları

Konumunuza en yakın Schneider Electric distribütörünü kolayca bulun.

Yardım Merkezi

Yardım Merkezi

Tüm ihtiyaçlarınız için destek kaynaklarını tek bir yerde bulun.

  • Ürün Belgeleri
  • Yazılım İndirmeleri
  • Ürün Seçici
  • İkame Ürün ve Değiştirme
  • Yardım Merkezi
  • Ofislerimizi Bulun
  • Teklif Alın
  • Satış noktaları
  • Schneider Electric Topluluğu
  • Kariyer
  • Şirket Profili
  • Bir usulsüzlüğü bildirin
  • Erişilebilirlik
  • Haberler
  • Yatırımcılar
  • EcoStruxure
  • İş Araması
  • Blog
  • Gizlilik İlkesi
  • Çerez Bildirimi
  • Change your cookie settings