Markalar

Schneider Electric Web Sitesine Hoş Geldiniz

Web sitemize hoş geldiniz.
		
Size bugün nasıl yardımcı olabiliriz?
How to Safely Distribute Database Folders to Another Disk/Location in Geo SCADA/ClearSCADA.
⚠️*Warning: This article contains information about editing the registry. Improper changes to the registry can permanently damage the operating system.
Always backup the registry before making any changes.*


In some cases, you may need to distribute Geo SCADA database folders (such as Config, Data, History, etc.) to different disks or locations for performance optimization or storage management. This can be achieved using the Registry Editor method. Below is a step-by-step guide.

Steps to Move Database Folders

Step 1: Shut Down the Geo SCADA Server

  • Right-click the Geo SCADA Server icon in the system tray.
  • Select Shutdown Server.


server shut down

Step 2: Locate the Original Database Folder

  • Navigate to the default database path:
    C:\ProgramData\Schneider Electric\ClearSCADA\Database
    Here you will find folders such as:
  • Config
  • ConfigChanges
  • Data
  • DataFiles
  • HisFiles
  • History
  • Journal
locate folder

Step 3: Move the Desired Folder

  • Copy or move the folder you want to relocate (e.g., ConfigChanges, History) to the new disk or location.

Step 4: Update the Registry

  • Open Registry Editor (regedit).
  • Navigate to:
    HKEY_LOCAL_MACHINE\SOFTWARE\Schneider Electric\ClearSCADA\DB
  • Locate the registry key corresponding to the folder you moved (e.g., ConfigChangePath, HistoryPath).
  • Update the Value data to the new folder path.

regitry

Step 5: Restart Geo SCADA Server

  • Start the Geo SCADA server again.
  • Verify the new folder location in Server Configuration → System configuration → Location.

server config

Best Practices

  • Ensure the new location has sufficient disk space and proper permissions.
  • Avoid moving folders while the server is running.
  • Keep a backup of the original database before making changes.

Schneider Electric Turkey

Daha fazlasını keşfedin
Seri:
Daha fazlasını keşfedin
Seri:
  • Ürün Belgeleri
  • Yazılım İndirmeleri
  • Ürün Seçici
  • İkame Ürün ve Değiştirme
  • Yardım Merkezi
  • Ofislerimizi Bulun
  • Teklif Alın
  • Satış noktaları
  • Schneider Electric Topluluğu
  • Kariyer
  • Şirket Profili
  • Bir usulsüzlüğü bildirin
  • Erişilebilirlik
  • Haberler
  • Yatırımcılar
  • EcoStruxure
  • İş Araması
  • Blog
  • Gizlilik İlkesi
  • Çerez Bildirimi
  • Change your cookie settings