How to Restore Default Password on PowerLogic P3 Relay
Issue:
Unable to restore the default password on PowerLogic P3 relay devices.
Product:
PowerLogic P3 Protection Relay
Environment:
- PowerLogic P3 relay with firmware version 30.111 or below
- PowerLogic P3 relay with firmware version above 30.111
- Tools: Easergy Pro and Vampset configuration tool
- Connection via COM port or Ethernet
Cause:
The default password cannot be restored without specific device information due to security measures implemented in the relay firmware.
Resolution:
For firmware version 30.111 or below:
1.- Connect to the relay and open eSetup Easergy Pro.
2.- Retrieve the following information by clicking on the READ Button:
- Break code
- VID number
3.- Send the above details along with nameplate information to your nearest Schneider Electric Customer Care Centre or SE Technical Support.
For firmware version above 30.111:
1.- Retrieve the following information:
- Cyberbasic details
- Firmware version
2.- Steps to get Cyberbasic details:
Download and install Vampset from Schneider Electric website: VAMPSET
3.- Open Vampset, select the correct COM port, and apply.
4.- Navigate to Communication → Terminal.
5.- Enter the following commands:
s pwd=54321
g cyberbasic
Copy the output details.
6.- To get the firmware version, refer to the relay’s configuration screen. The version should appear in the format 30.YYY-a (e.g., 30.205-0).
7.- Send all collected information to Schneider Electric Customer Care Centre or SE Technical Support.
Yayımlanma amacı: Schneider Electric Turkey
Yardıma mı ihtiyacınız var?
Ürün seçici
Uygulamalarınız için doğru ürünleri ve aksesuarları hızlı ve kolay bir şekilde bulun.
Teklif Alın
Satışla ilgili sorularınızı çevrimiçi olarak başlatın, bir uzman sizinle bağlantı kuracaktır.
Satış noktaları
Konumunuza en yakın Schneider Electric distribütörünü kolayca bulun.
Yardım Merkezi
Tüm ihtiyaçlarınız için destek kaynaklarını tek bir yerde bulun.