Markalar

Schneider Electric Web Sitesine Hoş Geldiniz

Web sitemize hoş geldiniz.
		
Size bugün nasıl yardımcı olabiliriz?
How to Configure Firewall Rules on SAGE RTU

Issue:

Need to secure network traffic by applying firewall rules on the RTU.

Product:

SAGE RTU with Config@WEB Secure Software

Environment:

  • Firmware version C3414-500-S02YZ or later
  • Access to Config@WEB GUI

Cause:

Unrestricted network access can expose the RTU to cybersecurity risks.

Resolution:

  1. Navigate to CPU Configuration → Configure Firewall.
  2. Click Configure Firewall button.
  3. Enter firewall rules using the syntax described in the Firewall Configuration Guide: "Wind River Firewall and NAT PROGRAMMER'S GUIDE 6.8" available at: https://www.windriver.com/
  4. Submit changes and reset the RTU for rules to take effect.

1

Schneider Electric Turkey

Daha fazlasını keşfedin
Seri:
Daha fazlasını keşfedin
Seri:
  • Ürün Belgeleri
  • Yazılım İndirmeleri
  • Ürün Seçici
  • İkame Ürün ve Değiştirme
  • Yardım Merkezi
  • Ofislerimizi Bulun
  • Teklif Alın
  • Satış noktaları
  • Schneider Electric Topluluğu
  • Kariyer
  • Şirket Profili
  • Bir usulsüzlüğü bildirin
  • Erişilebilirlik
  • Haberler
  • Yatırımcılar
  • EcoStruxure
  • İş Araması
  • Blog
  • Gizlilik İlkesi
  • Çerez Bildirimi
  • Change your cookie settings