How is the ATV12 programmed for a 0-10Vdc analog input on AI1?
Issue:
Programming an ATV12 for a 0-10Vdc analog input on AI1
Product Line:
ATV12
Environment:
Programming
Cause:
n/a
Resolution:
The factory default is for a 0-5Vdc input. Set AI1t = 10U to accommodate a 0-10V input. AI1t is found in the IO menu and AI1 submenu.
Programming an ATV12 for a 0-10Vdc analog input on AI1
Product Line:
ATV12
Environment:
Programming
Cause:
n/a
Resolution:
The factory default is for a 0-5Vdc input. Set AI1t = 10U to accommodate a 0-10V input. AI1t is found in the IO menu and AI1 submenu.
發佈於: 施耐德電機Taiwan