我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
What causes an E-Flex drive to trip on overheating fault OHF?
Issue:
E-Flex drive is tripping on OHF

Product line:
Altivar ATV61 E-Flex enclosed drives

Environment:
All models, all serial numbers

Cause:
Cooling fans are not running or the thermal sensor may be bad

Resolution:
Check the heat sink cooling fans to see if they are running.  If they are not running remove the fan connector and check to see if you have voltage on the terminals.  If you have good voltage then the heat sink cooling fans are bad. If you don't have voltage on the terminals you may have a bad power board and or drive.   To check the thermal sensor you can monitor the drives thermal temp % in Menu 1.2 monitoring. If the thermal % is jumping around erratic you may have a bad thermal sensor.

施耐德電機Taiwan

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings