我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
What can cause an (FrF) line frequency fault on the ATS48 Soft Starters?

Change Parameter FrC from AUt to 60.  This changes the tolerance to plus/minus 20%.

Remove and inspect the green terminal strips at the bottom of the softstart.  Securely reinstall the strips.

Confirm that control power is present on CL1-CL2 terminals before a Run command is given.  Delay the Run command until nLP or rdY codes appear on the display.

Is the power supply from a generator?.  If so, check the frequency of the line to see if it is out of tolerance.  Upgrade the generator if necessary.  The FrC setting accommodates Class 1, 2 or 3 generators as defined by the Electrical Generating Systems Association.

Contact the Drives Product Support Group if the fault continues after corrective action.

“If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)


施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings