我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Behavior of the logical outputs if they are written in different tasks.

Goals and Symptoms

Behavior of the logical outputs if they are written in different tasks.

Causes and Fixes

If local logical outputs are written in different tasks of the LMC (Auxiliary task, Motion task or event task) inconsistencies between the programmed value and the physical value of the output can occur.
- This behavior appears if the same output is written in different tasks but also if 2 different outputs are written in different tasks.
- This behavior is common to all the platforms running with Codesys and is not regarded as misbehavior.
- It cannot be modified
- Solution: use LMC_ExplicitOutput FB if you need to write logical outputs from different tasks of the LMC.

Attachments

(Removed File URL: 198428_B832/Behaviour_of_the_logical_outputs_V1_.zip)(Removed Image URL: /PubResEXPORT.nsf/2b87ee90be777fc085257c28006ee4ef/ef76aab6e13c647cc12575ad005297d5/fl_block_5/0.64E?OpenElement&FieldElemFormat=gif)


Legacy KB System (APS) Data: RESL198428 V1.0, Originally authored by MaPr on 05/05/2009, Last Edited by MaPr on 05/05/2009
Related ranges: Lexium Controller

施耐德電機Taiwan

附件
Behaviour_of_the_logical_outputs_V1_.zip [73.67 KB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings