Behavior of the logical outputs if they are written in different tasks.
Goals and Symptoms
Behavior of the logical outputs if they are written in different tasks.
Causes and Fixes
If local logical outputs are written in different tasks of the LMC (Auxiliary task, Motion task or event task) inconsistencies between the programmed value and the physical value of the output can occur.
- This behavior appears if the same output is written in different tasks but also if 2 different outputs are written in different tasks.
- This behavior is common to all the platforms running with Codesys and is not regarded as misbehavior.
- It cannot be modified
- Solution: use LMC_ExplicitOutput FB if you need to write logical outputs from different tasks of the LMC.
Attachments
(Removed File URL: 198428_B832/Behaviour_of_the_logical_outputs_V1_.zip)(Removed Image URL: /PubResEXPORT.nsf/2b87ee90be777fc085257c28006ee4ef/ef76aab6e13c647cc12575ad005297d5/fl_block_5/0.64E?OpenElement&FieldElemFormat=gif)
Legacy KB System (APS) Data: RESL198428 V1.0, Originally authored by MaPr on 05/05/2009, Last Edited by MaPr on 05/05/2009
Related ranges: Lexium Controller
發佈於: 施耐德電機Taiwan






需要協助?
產品選型工具
快速輕鬆地為您的應用找到合適的產品和附件。
取得報價
立即線上提交您的銷售需求,專業團隊將主動聯繫您。
購買地點
輕鬆在您所在地區找到最近的施耐德電機經銷商。
支援中心
在同一位置找到滿足您所有需求的支援資源。