我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Can I lose my alarms log in Vijeo Designer when power cycling my Harmony HMI,?

Issue
Will I lose my alarms log in Vijeo Designer when power cycling my Harmony HMI?

Product Line
Vijeo Designer, XBTGT, XBTGK, HMIGTO, HMIGK, HMIG2U, HMIG3U

Environment
HMI Programming Software for Windows and Physical HMI

Resolution
Each alarm group can have 2 types of alarm buffers:
(1) one for History Alarm events (size defined by the "Num of History Alarms" property) and
(2) one for Log Alarm events (size defined by the "Num of Log Alarms" property).

These alarm buffers are stored by default in the DRAM (Dynamic RAM: similar to the RAM of a PC) of the HMI Target. Therefore, if the target is turned off, the alarm buffers will be cleared from the memory.

If you need them to be saved even when the HMI power is turned off, you can activate the "Backup Alarm Group" property (at the global alarm level).
This way, these alarm buffers will be stored in the DRAM and in the SRAM (Static RAM: doesn't get wiped out when the target is turned off) as well.

Since the size of these alarm buffers is limited (the maximum value for the "Num of History Alarms" and "Num of Log Alarms" properties is 10000), they won't always contain the whole history of alarm events on the target. To obtain that behavior, you can activate the "Save To File" property (at the alarm group level). This way, the alarm events will be saved into Excel CSV files (on the CF card) and these Excel files will contain the whole history of alarm events for the corresponding alarm groups.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings