Object Requirement for CANopen STBNCOxxxx Islands
Issue
The purpose of this resolution is to remind CANopen network users of an important object that is required when STBNCOxxxx interfaced islands have analog modules installed in them.
Product Line
Advantys, STB
Resolution
According to CANopen standard DS-401, PDO transmission of analog input data is only possible if object 6423h is set to 1. Per the standard, default for this object is disabled (sections 6.2.7, 6.2.9 and 6.2.11).
Causes and Fixes
The following is an excerpt from STBNCO2212 documentation: