Procedure for adding an IP address onto a ProworX32 project for a Momentum 171CCC9x0 x0 M1E processor.

Goals and Symptoms

Procedure for adding an IP address onto a ProworX32 project for a Momentum 171CCC9x0 x0 M1E processor.

Causes and Fixes


· Start up ProworX32
· Open your project


· Select Configuration


· Enter a value into the Config Extension Size (ex. 200)
· This value can be modified later depending on the Config Extension Used value


· Select Configuration Extensions
· Check and highlight TCP/IP
· Enter New IP and Subnet Mask info


· Save project


· Select Communications
· Select which form of connection you currently have to download your project.(Modbus, Modbus Plus or TCP/IP)
· Or enter the PRODUCTS current IP address that is stored on the processor if your just changing to a new IP address.


· Save project


· Open Controller tab
· Select Write All


· Select Write


· Make sure you get the Write to M1 960-20 Complete in the Message Central window


· Select Communications
· Enter New IP address info


· Open Controller tab
· Select Transfer to Flash/EEPROM…


· Select Transfer


· Select Yes to stop the controller

· Make sure you get the Write to M1 960-20 Complete in the Message Central window
· Recycle power to your Momentum processor to make sure all changes were saved


· When the processor powers up and the LAN LED on the processor stays on steady try to ping the new IP address

· Open Controller tab
· Select Start/Stop…

· Select Start

· Make sure you get the Controller is Running in the Message Central window
· Check your logic and make sure all is fine

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings