我们今天能为您提供什么帮助?

Control Expert (formerly Unity Pro) is generating a "Task Overrun" error which sets %S19 . What is the most likely cause of this error?

Issue:

Control Expert (formerly Unity Pro) is generating a "Task Overrun" error which sets %S19 . What is the most likely cause of this error?

Product Line:

Control Expert (formerly Unity Pro)

Resolution:

The Task Overrun error (%S19) is set to 1 when the time it takes to complete a Task exceeds the specified time.
The MAST & FAST Task's use the WDT setting to determine when %S19 will set. The user must reset this bit to 0.

Note : If this happens repeatedly, the program may be need to be reviewed. For instance, the program may have for loop in a ST section that does not exit the loop properly and that could cause a watchdog over run. If it is not the program then the Hardware needs to be set for a TEX.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

施耐德電機Taiwan

探索更多

探索更多

需要協助?

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

在同一位置找到滿足您所有需求的支援資源。