PM820 Date and Time Can Not be Changed

Issue
Unable to change the date and time of a PM820 meter.

Product
PM820 - Series 800 Power Meter

Environment
PM820
Firmware Version 10.310

Cause
This problem has been identified only on a PM820 with firmware version 10.310.

Resolution

There are 2 possible solutions.
First solution: Upgrade the firmware to version 10.410 or greater.

Access to firmware upgrade instructions can be found here, and a how-to video and a link to the latest firmware
can be found at: How to upgrade firmware on a PM800 series meter from version OS 10.060 or below to the latest version | Schneider Electric USA

Additionally, supporting documents and file downloads on this and a wide variety of other products and topics may be obtained
using the search function found at the: Download Center


Second solution: apply the following procedure:
To change the time, you have to:

1) change "HOUR"
2) press "OK"
3) change "MIN"
4) press "OK"
5) change "SEC"
6) press "OK"
7) change desired time format (24H or AM/PM)
8) DO NOT press "OK"; instead press UP ARROW button (left softkey)

NOTE: If format was changed then UP ARROW again and you will be prompted to save; Else you're done.

To change the date, you have to:

1) change "MONTH"
2) press "OK"
3) change "DAY"
4) press "OK"
5) change "YEAR"
6) press "OK"
7) change desired date format
8) DO NOT press "OK"; instead press UP ARROW button (left softkey)

NOTE: If format was changed then UP ARROW again and you will be prompted to save; Else you're done.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings