Register containing count integrator roll-overs count required for the ION6200

Issue
There are no roll-over count registers available for the integrator modules on the ION6200.

Product Line
ION6200

Cause
The ION6200 is slightly different than other ION devices in that most of its configuration parameters are hard-coded into the device and cannot be modified. The ION6200 is not a "true ION" device. Yes, there are "integrator modules" however these modules have hard-coded registers, and not all of the same output registers are available like on the ION73xx and high devices. Only the total accumulated value is available.

Resolution
If a roll-over count is required there are some alternative solutions:

  1. If using an ION device to Modbus Master an ION6200, create a Modbus register map to read a power register(kW tot, kVAR tot...) and add an integrator module on the ION device ( Modbus Master). Link this register to the integrator module and configure this module accordingly.
  2. Use the VIP. Create an integrator Module in the VIP linked to a power register(kW tot, kVAR tot...) from an ION6200 and configure this module accordingly.
To avoid losing any resolution of the energy accumulated value it is recommended that the rollover be set to 10 000 000. This default roll-over value is set at this number because it is a convenient number that is easier to remember than 16777215 (=2^24-1) which is the absolute limit imposed by the 32bit IEEE register format without loss of resolution on the stored number. For more detail as to why this is so, see https://www.se.com/us/en/faqs/FA204140/

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings