Error while generating web report: The Sort expression for the table 'shiftDescriptionTable' contains an error: Conversion from string "12:00 a.m." to type 'Date' is not valid.

Issue:

Generating a web report fails with the following error:

An error had occurred during report processing. The Sort expression for the table ‘shiftDescriptionTable’ contains an error: Conversion from string “12:00 a.m.” to type ‘Date’ is not valid.

Product Line:

Power Monitoring Expert 9.0

Power Monitoring Expert 2020

Power Monitoring Expert 2021

Power Monitoring Expert 2022

Power Monitoring Expert 2023

Power Monitoring Expert 2024

Environment:

Web Reports (browser-rendered)
Internet Explorer installed on the reporting host or client

Cause:

Internet Explorer version 6 or older is installed and is not a supported browser for this Web Reports deployment. The legacy browser fails when the report engine sorts fields containing AM/PM time strings (for example, “12:00 a.m.”), which results in the conversion-to-Date error.

Resolution:

  1. Check the installed browser version on the Web Reports host (and any client used to render reports).
  2. Upgrade Internet Explorer to a supported version (IE 7 or newer) on the affected machine(s).
  3. Re-test web report generation.
  4. Optional: If reports still fail, clear the browser cache and restart the reporting service (or IIS, if applicable), then test again.

Supported web browsers (latest PME version)

  • Google Chrome (version 100)
  • Mozilla Firefox (version 128)
  • Microsoft Edge
  • Apple Safari (versions 7 or 8)

Note: Changing regional time format and rebooting does not resolve this issue if the underlying browser version is unsupported.

Recommendation:

If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com

PME Version History

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings