我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Changing the default color of the Stale and Erroneous Data indicator Flags (Orange and Yellow boxes) in Vista

Issue
Vista Diagram Objects appear in yellow and orange boxes.

Product Line
ION Enterprise 6.x
StruxureWare Power Monitoring 7.0.x
Power Monitoring Expert 7.2.x
Power Monitoring Expert 8.x
Power Monitoring Expert 9.0
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023



Cause
Objects containing erroneous and stale data are colored and marked by Vista. (yellow and orange boxes around objects)
Default Flags:
Yellow – Stale Data
Orange – Erroneous Data

Resolution
*Perform backups before modifying your system
These colors can be changed on a per user basis.
To edit these colors open the user configuration file

ION Enterprise file path: (user.wsu) in ...\ION Enterprise\config\cfg\ud
Power Monitoring Expert file path: (supervisor.wsu) in ...\Power Monitoring Expert\config\cfg\ud

For this example, guest.wsu is being used.
Edit the file in Notepad and look for the following tags:

<StaleFlagColor>#ffff00</StaleFlagColor>
<ErrorFlagColor>#ff8000</ErrorFlagColor>

The hex string in the tags represent the color of the boxes in Vista. These can be edited to be any hex color. To find more information on hex color codes please see the link: http://en.wikipedia.org/wiki/Web_colors

For example, if we wanted to use Red (#ff0000) for stale data and Green (#008000) for erroneous data the file would look like this:

<StaleFlagColor>#ff0000</StaleFlagColor>
<ErrorFlagColor>#008000</ErrorFlagColor>

Once you have made the changes save the file, open the file properties and mark the file as Read Only. This will prevent ION Enterprise from changing this file back to the default the next time the user logs in.

guest.wsu

vista
vista

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings