我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
ION Setup cannot communicate with meters using an RS485/RS232 converter

Issue
Old ION Setup version sometimes cannot communicate with meters using RS485/RS232 converter. Even though the ION Enterprise can communicate with the same physical connection.

Product Line
ION Setup

Environment
Power Monitoring Expert (PME)
ION Setup
Modbus mastering

Cause
Older versions of ION Setup uses a "processor" oscillation count to compute high accuracy millisecond timing. Now with dual and quad core processors, it can return different values depending on which processor is active when ION:S queries the value. Thus, instead of waiting 'X' ms to transmit... it does it immediately, causing issues.

The latest version of ION:S uses multi-media timers (similar to the one used in playing MOV files and such) and which have their own issues when under heavy loading (i.e. when playing MOVs, you sometime get jerky effects due to Windows being busy) but there are no other solutions that are acceptable and can be easily coded.

Resolution
Update ION Setup to the latest version.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings