Cannot open VIP in Designer

Issue
The issue should tell what the article is about and briefly describe what's going on =>ex: the error message that pops up or is in the system log, general things that the reader may see happening with they're system/device to indicate this issue

Product Line
Power Monitoring Expert 7.2.2
Power Monitoring Expert 8.2
Power Monitoring Expert 9.0
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024

Environment
Designer

Cause #1
When the user tries to open the VIP in Designer an error message is displayed which says, "Communications error, solve the problem and try again." Additionally, the ION Virtual Processor Service is not running.
Communication Error

Cause # 2
When the user tries to open the VIP in Designer an error message is displayed which says, "Communications error, solve the problem and try again." Additionally, the ION Virtual Processor Service is not running and cannot be started.

Resolution #1
Designer can't open the VIP because it is not running.
Services
Resolution #2
The VIP is not running because both the vip.cfg and vip.bak files are corrupt. The current vip files (both .cfg and .bak in \config\cfg\vip\) should be deleted as well as the node diagram file (in \config\diagrams\nd). Then, when the ION Virtual Processor Service is started, a new, blank VIP will be created.
Use article: Restoring VIP | Schneider Electric Global (se.com)

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings