Struxureware Power Monitoring 7.0.1 - Why do the PM5350, PM3200, Em3100/3200 and EM7000 devices show negative values in the energy accumulators?

Issue
Devices show negative values in the energy accumulators

Product Line
PM5350, PM3200, EM3100/3200, EM7000

Environment
PME 7.0.1

Resolution
When the values contained in the energy accumulator get large - in the range of GWh/GVAh/GVARh), there is a problem with the PM3200, PM5350, EM3100/3200 and EM7000 drivers where it does not interpret the value correctly. Instead of the correct value, a large negative number is displayed. Note that the value displays correctly on the front panel of the device, or when read via a third party modbus master. The problem is not with the device itself, but rather with the driver.

The S64-87-21 format used by the energy values was not interpreted correctly by the driver and displayed incorrect negative values. This has been fixed in the drivers and updated drivers have been posted on the Schneider-electric website.

For existing installations, the driver dll will need to be replaced. See attached zip files for hotfixes with instructions for all the affected drivers.

This problem affects the following drivers:

EM7000 Series SE 7.0.1.12353.01

iEM3100_3200 Series SE 7.0.1.12295.03

PM3200 Series SE 7.0.1.12291.01

PM5350 SE 7.0.1.13048.01

EM7000 Series SPM 7.0.1 Negative Energy patch.zipEM7000 Series SPM 7.0.1 Negative Energy patch.zipiEM3100_3200 Series Negative Energy patch.zipiEM3100_3200 Series Negative Energy patch.zip

PM3200 Series SPM 7.0.1 Negative Energy patch.zipPM3200 Series SPM 7.0.1 Negative Energy patch.zipPM5350 SPM 7.0.1 Negative Energy patch.zipPM5350 SPM 7.0.1 Negative Energy patch.zip

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings